Electric measuring devices (A-meters and V-meters) of E47 series

Description


These devices are applied in low-voltage complete devices are used in distribution electric circuits of residential, commercial and industrial objects.

E47 A-meters are analog electromagnetic devices designed for measuring current in AC networks.

E47 V-meters are analog electromagnetic devices designed for measuring voltage in AC networks.

Electric measuring devices of E47 series correspond to the requirements of IEC 61010-1, IEC 61326.

E47 electric measuring devices are introduced into the State register of measuring equipment under No. 39231-08. Establishment certificate of measuring equipment CN.C.34.010A No. 33523.

Operating Principle

A-meters and V-meters are devices with an electromagnetic system. They consist of a round coil with movable and rigid cores inside. When current flows through the coil windings, it creates an electromagnetic field magnetizing both cores making the similar core poles repel and axis with a needle spin. For protection from the negative influence of external magnetic fields, the coil and both cores are covered with a metal shield.

Range


 
Type Actuation method Accuracy class Rated operating voltage, V Front panel size, mmMultiple package amount, pcs Product ID
A-meters
A-meter E47 10 72x72 mm Direct 1,5 400 72x72 100 IPA10-6-0010-E
A-meter E47 50 72x72 mm 1,5 400 72x72 100 IPA10-6-0050-E
A-meter E47 100/5 72x72 mm Through the current transformer with secondary current of 5A 1,5 400 72x72 100 IPA10-6-0100-E
A-meter E47 150/5 72x72 mm 1,5 400 72x72 100 IPA10-6-0150-E
A-meter E47 200/5 72x72 mm 1,5 400 72x72 100 IPA10-6-0200-E
A-meter E47 300/5 72x72 mm 1,5 400 72x72 100 IPA10-6-0300-E
A-meter E47 400/5 72x72 mm 1,5 400 72x72 100 IPA10-6-0400-E
A-meter E47 600/5 72x72 mm 1,5 400 72x72 100 IPA10-6-0600-E
A-meter E47 1000/5 72x72 mm 1,5 400 72x72 100 IPA10-6-1000-E
A-meter E47 1500/5 72x72 mm 1,5 400 72x72 100 IPA10-6-1500-E
A-meter E47 2000/5 72x72 mm 1,5 400 72x72 100 IPA10-6-2000-E
A-meter E47 3000/5 72x72 mm 1,5 400 72x72 100 IPA10-6-3000-E
A-meter E47 10 96x96 mm Direct 1,5 400 96x96 60 IPA20-6-0010-E
A-meter E47 50 96x96 mm 1,5 400 96x96 60 IPA20-6-0050-E
A-meter E47 100/5 96x96 mm Through the current transformer with secondary current of 5A 1,5 400 96x96 60 IPA20-6-0100-E
A-meter E47 150/5 96x96 mm 1,5 400 96x96 60 IPA20-6-0150-E
A-meter E47 200/5 96x96 mm 1,5 400 96x96 60 IPA20-6-0200-E
A-meter E47 300/5 96x96 mm 1,5 400 96x96 60 IPA20-6-0300-E
A-meter E47 400/5 96x96 mm 1,5 400 96x96 60 IPA20-6-0400-E
A-meter E47 600/5 96x96 mm 1,5 400 96x96 60 IPA20-6-0600-E
A-meter E47 1000/5 96x96 mm 1,5 400 96x96 60 IPA20-6-1000-E
A-meter E47 1500/5 96x96 mm 1,5 400 96x96 60 IPA20-6-1500-E
A-meter E47 2000/5 96x96 mm 1,5 400 96x96 60 IPA20-6-2000-E
A-meter E47 3000/5 96x96 mm 1,5 400 96x96 60 IPA20-6-3000-E
V-meters
V-meter E47 100 72x72 mm Direct 1,5 600 72x72 100 IPV10-6-0100-E
V-meter E47 300 72x72 mm 1,5 600 72x72 100 IPV10-6-0300-E
V-meter E47 500 72x72 mm 1,5 600 72x72 100 IPV10-6-0500-E
V-meter E47 600 72x72 mm 1,5 600 72x72 100 IPV10-6-0600-E
V-meter E47 100 96x96 mm 1,5 600 96x96 60 IPV20-6-0100-E
V-meter E47 300 96x96 mm 1,5 600 96x96 60 IPV20-6-0300-E
V-meter E47 500 96x96 mm 1,5 600 96x96 60 IPV20-6-0500-E
V-meter E47 600 96x96 mm 1,5 600 96x96 60 IPV20-6-0600-E

Advantages


  • Wide scale range: A-meters up to 3000A, V-meters up to 600V.
  • Accuracy class 1.5.
  • All A-meter and V-meter modifications are supplied in two dimensions: 72x72 and 96x96 mm.
  • Board panel installation.
  • Electrical safety.
  • Inspection period 2 years.

Design Features


Assembly parts: nuts, machine screws, plastic holders for installing onto the board panel included in the delivery set ensure easy mounting without applying additional tools. Transparent protective cover shielding on external connecting terminals ensures electrical safety.
Body sealing prevents unauthorized access to the device’s mechanism. Devices are supplied with a mechanic tool adjusting the needle’s zero position.
A-meters for measuring currents exceeding 50A are connected to the measured circuit using a current transformer with the rated secondary operating current of 5A.
Metal shield protects the electromagnetic system from external magnetic fields.  
 

Technical Features


Feature

E47 A-meters

E47 V-meters

System

electromagnetic

electromagnetic

Data input

analog

analog

Scale range

0÷3000A

0÷600V

Installation method

onto the board panel

onto the board panel

Actuation method

≤ 50A - direct

direct

≥ 100A - through the current transformer with secondary current of 5A

Accuracy class

1,5

1,5

Main error limit, %

±1,5

±1,5

Max. rated operating voltage

400V

600V

Possible long-term overloading (limited to 2 hours)

120% from the max. scale range

120% from the max. scale range

MTTF, not less than, hours

65000

65000

Average service life, not less than, years

8

8

Ambient temperature, C

20±1,5

20±1,5

Measurable value frequency, Hz

45÷65

45÷65

Mounting plane position

vertical

vertical

Weight, kg

72x72mm 0,164

72x72mm 0,164

96x96mm 0,238

96x96mm 0,238

Overall Dimensions


Front panel size, mm , mm L, mm 1, mm 2, mm
72x72 72 72 66 68
96x96 96 96 90 92