Air circuit breakers VA07

Description


VA07 circuit breakers are installed into transformer substations, switch and control gears and main distribution boards as lead-in, sectional and distribution units for connecting and protecting drives, generators, transformers, buses and cables at industrial and residential construction sites, electric supply of high technology manufactures, banks and utilities. They are intended for exploitation in electric units with rated operating voltage limited to 690V per rated current from 800 to 4000A.

These ACB correspond to the requirements of IEC 60947-2.

Range


Name Rated current, A Number of poles Ultimate short-circuit breaking capacity IcuTransport package amount, pcs Product ID
Draw-out CB 07 208 with undervoltage trip 3P 800 65 kA IEK 800 3 50 1 SAB230 0800 U11H P11
Draw-out CB 07 208 with shunt trip 3P 800 65 kA IEK 800 3 50 1 SAB230 0800 S11H P11
Draw-out CB 07 208 undervoltage trip 3P 800 65 kA IEK 800 3 50 1 SAB231 0800 U11H P11
Draw-out CB 07 208 with shunt trip 3P 800 65 kA IEK 800 3 50 1 SAB231 0800 S11H P11
Draw-out CB 07 212 with undervoltage trip 3P 1250 65 kA IEK 1250 3 50 1 SAB230 1250 U11H P11
Draw-out CB 07 212 with shunt trip 3P 1250 65 kA IEK 1250 3 50 1 SAB230 1250 S11H P11
Draw-out CB 07 212 undervoltage trip 3P 1250 65 kA IEK 1250 3 50 1 SAB231 1250 U11H P11
Draw-out CB 07 212 with shunt trip 3P 1250 65 kA IEK 1250 3 50 1 SAB231 1250 S11H P11
Draw-out CB 07 216 with undervoltage trip 3P 1600 65 kA IEK 1600 3 50 1 SAB230 1600 U11H P11
Draw-out CB 07 216 with shunt trip 3P 1600 65 kA IEK 1600 3 50 1 SAB230 1600 S11H P11
Draw-out CB 07 216 undervoltage trip 3P 1600 65 kA IEK 1600 3 50 1 SAB231 1600 U11H P11
Draw-out CB 07 216 with shunt trip 3P 1600 65 kA IEK 1600 3 50 1 SAB231 1600 S11H P11
Draw-out CB 07 220 with undervoltage trip 3P 2000 65 kA IEK 2000 3 50 1 SAB230 2000 U11H P11
Draw-out CB 07 220 with shunt trip 3P 2000 65 kA IEK 2000 3 50 1 SAB230 2000 S11H P11
Draw-out CB 07 220 undervoltage trip 3P 2000 65 kA IEK 2000 3 50 1 SAB231 2000 U11H P11
Draw-out CB 07 220 with shunt trip 3P 2000 65 kA IEK 2000 3 50 1 SAB231 2000 S11H P11
Draw-out CB 07 325 with undervoltage trip 3P 2500 85 kA IEK 2500 3 65 1 SAB330 2500 U11H P11
Draw-out CB 07 325 with shunt trip 3P 2500 85 kA IEK 2500 3 65 1 SAB330 2500 S11H P11
Draw-out CB 07 325 undervoltage trip 3P 2500 85 kA IEK 2500 3 65 1 SAB331 2500 U11H P11
Draw-out CB 07 325 with shunt trip 3P 2500 85 kA IEK 2500 3 65 1 SAB331 2500 S11H P11
Draw-out CB 07 332 with undervoltage trip 3P 3200 85 kA IEK 3200 3 65 1 SAB330 3200 U11H P11
Draw-out CB 07 332 with shunt trip 3P 3200 85 kA IEK 3200 3 65 1 SAB330 3200 S11H P11
Draw-out CB 07 332 undervoltage trip 3P 3200 85 kA IEK 3200 3 65 1 SAB331 3200 U11H P11
Draw-out CB 07 332 with shunt trip 3P 3200 85 kA IEK 3200 3 65 1 SAB331 3200 S11H P11
Draw-out CB 07 440 with undervoltage trip 3P 4000 100 kA IEK 4000 3 75 1 SAB430 4000 U11V P11
Draw-out CB 07 440 with shunt trip 3P 4000 100 kA IEK 4000 3 75 1 SAB430 4000 S11V P11

Advantages


  • High rated breaking capacity ratings up to 100kA.
  • Equal ratings of service and ultimate short-circuit breaking capacity: Ics=Icu.
  • Expanded standard configuration.
  • Maximum saved space inside the distribution board.
  • Equal bay in the panel door independently from the ACB dimensions.
  • Heightened number of power cycles up to 30 000 cycles.
  • Possibility to change main contacts.
  • Fast arc extinguishing owing to Double Break system.
  • Small dissipated power value.
  • Expanded range of selectivity.
  • Raised exploitation safety.
  • Special type option for use in tropical and cold climate conditions as well as corrosive environments.

Design Features


All unit types with rated current limited to 3200A have equal depth (345 mm) and height (460 mm). Panel door bay dimensions are equal for any VA07ACB that facilitate its mounting inside the distribution board.

Using an electronic release ensuring performing the following functions:

- protection from long-term overload;
- short circuit protection;
- adjustable instantaneous trip function.

“Double Break” system guarantees fast short circuit arc-breaking at the expense of dividing it in two with the help of making breaks in two point of every pole. As a result, it provides for lowering the contacts’ wear resistance and erosion. Using two transformers on each pole. The first transformer is linear. It is responsible for current signal control. It ensures high accuracy class within the whole short-circuit currents range. The second transformer is intended for the electronic trip input.
Basic shipment configurations predetermine that main contacts type for units per current up to 3200A is horizontal, up to 4000 – vertical. Front and combined connection are optional. Main contacts can be easily changed to new ones. It provides for extending the ACB service life. Changing each contacts takes no longer than 15 minutes.

Technical Features


Feature VA07-208 VA07-212 VA07-216 VA07-220 VA07-325 VA07-332 VA07-440
Number of poles 3 3 3 3 3 3 3
Peak rated current In, A 800 1250 1600 2000 2500 3200 4000
Rated electronic trip unit current, 100≤In≤200
200≤In≤400
400≤In≤800
200≤In≤400
400≤In≤800
630≤In≤1250
200≤In≤400
400≤In≤800
630≤In≤1250
800≤In≤1600
200≤In≤400
400≤In≤800
630≤In≤1250
800≤In≤1600
1000≤In≤2000
1250≤In≤2500 1600≤In≤3200 2000≤In≤4000
Rated insulation voltage Ui, V 1000 1000 1000 1000 1000 1000 1000
Operating voltage (50/60Hz) Ue, V 690 690 690 690 690 690 690
Main circuit contacts DC internal resistance per pole (mΩ/pole) 0,033 0,033 0,028 0,024 0,014 0,014 0,014
Power consumption, VA (for 3-pole ACB) 200 350 350 490 600 780 1060
Ultimate rated short-circuit breaking capacity (lcs = lcu), kA AC 690V 50 50 50 50 65 65 75
AC 440V 65 65 65 65 85 85 100
Rated short-circuit making capacity Icm, kA ~690 V 105 105 105 105 146 146 165
~440 V 143 143 143 143 187 187 220
Rated short-time withstand current (1 sec.), lcw, kA 65 65 65 65 85 85 100
Mechanical wear resistance, power cycles with maintenance 30000 30000 30000 25000 20000 20000 15000
no maintenance 15000 15000 15000 12000 10000 10000 8000
Electrical wear resistance, power cycles no maintenance AC 440 V 12000 12000 12000 10000 7000 7000 3000
AC 690 V 10000 10000 10000 7000 5000 5000 2500
Weight max., kg 73 73 76 79 105 105 139

Overall Dimensions


Fixed Type

Dimensions VA07 208 VA07 212 VA07 216 VA07 220 VA07 325 07 332 VA07 440
a 360 360 360 360 466 466
b 460 460 460 460 460 460
c 290 290 290 290 290 290
d 75 75 75 75 75 75


Draw-out Type

Dimensions VA07 208 VA07 212 VA07 216 VA07 220 VA07 325 VA07 332 VA07 440
a 354 354 354 354 460 460 631
b 460 460 460 460 460 460 460
c 345 345 345 345 345 345 375
d 40 40 40 40 40 40 53

Configuration





Shunt trip unit Undervoltage trip unit Starting coil



Motor control Power cycle counter Auxiliary contact block